Fire Shutters
Inspection, Test and Routine Servicing
Automatic Operation - The following provisions shall be made for a fire-resistant roller shutter to automatically close in the event of fire. The operating mechanism shall -
(a) incorporate a fail-safe fusible link in accordance with Clause 5.6 that is legibly marked with a temperature rating not greater than 80°C (57°C in the case of a drenched shutter);
NB: Fire-resistant roller shutters may be set up to operate when activated by a smoke detector, heat detector or fire alarm. Nevertheless, a fusible link should be used in all fire-resistant roller shutters. Actuation by smoke, heat detector or fire alarm are secondary options only.
Where You Can Go To See What Is Fully Required To Comply?
Maintenance Standard
AS1851.Section 12.4.5
Minimum Standards of Performance
AS1905.2-2005
AS1905.2-1989
AS1905.2-1981
.
Inspection Intervals
All routine inspected and tested shall be in accordance with AS1851-2012.
Equipment Type | 3 Monthly | 6 Monthly | Yearly |
---|---|---|---|
Motorized Windows and shutters |