Automatic fail-safe devices

 
 
2 Automatic fail-safe devices 1.jpg

inspection, test and routine servicing

  1. The basis of inspection, testing and routine servicing of fire detection and alarm systems is to make sure that all the systems are operating and functioning correctly and to the relevant Standards.

What are Automatic fail-safe devices?

i) Magnetic door trips

ii) Mechanical air-conditioning trips

iii) Smoke and Heat Ventilation

iv) Natural Gas Trips

v) Gas Suppression

Where you can go to see what is fully required to comply -

a.     AS1851-2012 Appendix D – System Interface Testing

b.     AS1851-2012 Section 6 – Fire Detection and Alarms

 

Inspection Intervals

Automatic fail-safe devices these test will alter depending on the routine of other testing measures within AS1851.1.

As below here are some of the deference when testing these measures.

2 Automatic fail-safe devices 1.png
Equipment Type 3 Monthly 6 Monthly Yearly
Front door trips for make-up air
Magnetic Door Holders
Sliding Fire Door Holders
Mechanical Air-conditioning Trip
Smoke and Heat Ventilation Trips
Natrual Gas Shut-off
Gas Suppression
 
 
automatic fail safe 1.PNG

Sliding Fire Doors

Sliding fire doors have a magnetic door holder which holds the door in the open position. Sliding Doors are very heavy and we have seen a lot of these doors with inappropriately sized 50kg Magnetic Door Holders instead of measuring what is the weight of the door in the open position, then choosing the correct size magnet to hold the door open. Another example of seeking lower cost over correct performance.

There are magnets to suit the sliding door to be held open, starting from 50Kg, 100Kg, 150Kg & upwards.

Has your sliding door got the correct magnet??