Solid Core Door
Inspection, Test and Routine Servicing
NCC/BCA NSW C3.11(d).
(d) Protection for a doorway must be at least—
(i) in a building of Type A construction — a self-closing –/60/30 fire door; and
(ii) in a building of Type B or C construction—a self-closing, tight fitting, solid core door, not less than 35 mm thick, except—
(iii) in a Class 3 building used as a residential care building protected with a sprinkler system complying with Specification E1.5—
(a) a tight fitting, solid core door not less than 35 mm thick if the building is divided into floor areas not exceeding 500 m2 with smoke proof walls complying with Clause 2 of Specification C2.5; or
(b) a tight fitting, solid core door not less than 35 mm thick fitted with a self-closing device, a delayed closing device or an automatic closing device.
Where you can go to see what is fully required to comply?
Maintenance Standard
AS1851-2012 Section 12 – Passive Fire and Smoke Systems
Minimum Standards of Performance
BCA 20__ Spec C3.4
Inspection Intervals
All routine inspected and tested shall be in accordance with AS1851-2012
Equipment Type | 3 Monthly | 6 Monthly | Yearly |
---|---|---|---|
Smoke doors | |||
Solid Core Doors |